Coupled Electro-Thermal and Storage Dynamics of AM0 Photovoltaic Systems Supplying Megawatt-Scale Space Data Centers: A Simulation-Based Design Study

Authors

DOI:

https://doi.org/10.66104/sdhm5c86

Keywords:

AM0 photovoltaics, Constant-power load, High-voltage space bus, Maximum power point tracking, Orbital data centers, Square-root unscented Kalman filter

Abstract

This paper presents an exploratory simulation-based design study of a 1 MW electrical power subsystem (EPS) for a conceptual space data center in sun-synchronous low Earth orbit (SSO-LEO). The architecture integrates a 3850 m² triple-junction photovoltaic array, a 2.5 MWh battery energy storage system (BESS), and a 400 V HVDC bus supplying constant-power computing loads (CPL). The photovoltaic model is calibrated to 1.6872 MW under 25 °C AM0 reference. Periodic orbital thermal cycling (-92.6 °C to +54.1 °C, with a 144.3 K/min exit transient) reduces sunlight energy collection to 1.5972 MWh against a continuous-operation requirement of 1.6627 MWh (operating generation dropping to 1.5509 MW), yielding an orbital energy margin of -3.9% and an analytical preliminary scaled area of 4008 m² (+4.1%). Thus, while 3850 m² serves as the unadjusted standard reference baseline at 25 °C AM0, the final recommended operational flight array aperture is 4008 m² to ensure full energy closure under hot-orbit conditions. In the post-eclipse tracking window, temperature-compensated predictive MPPT (TC-PMPPT) achieves 98.46% tracking efficiency (+4.78 pp over nominal P&O at Ts = 1.0 s), demonstrating reduced step-size sensitivity across parameter sweeps rather than universal efficiency dominance, as tuned classic methods match it at fast sampling (Ts = 0.2 s). For battery state estimation, selective innovation-driven adaptation restricted to the ohmic resistance process-noise channel (Q(R0)) prevents covariance divergence, achieving zero non-finite runs across an extensive 500-seed Monte Carlo evaluation (0.00% divergence rate vs 8.80% for full-covariance fading UKF) and a high-precision nominal state-of-charge RMSE of 0.297% ± 0.039%. For bus stability, undamped constant-power loads precipitate Middlebrook instability; parallel RC damping with n ≥ 4 satisfies the 6 dB impedance margin. Large-signal 1.0 to 2.2 MW step simulations show that a transient nadir of 344.7 V (55.3 V dip) drives instantaneous load current to 6.38 kA (exceeding the 6.0 kA converter limit), but the system recovers without collapse because the damping capacitor bank supplies the transient deficit current. A 2 kHz PI controller with feedforward achieves the best dynamic recovery. In the equal-power dry mass budget, total mass is reduced by 62.8% (from 46,712 kg to 17,360 kg, saving 29,352 kg), of which 5.16 t is directly attributable to the 400 V bus and GaN conversion. Planar laminated busbars and dynamic charge-recovery hold-up bounds limit required capacitance to 32.5--35.0 mF, far below unoptimized reactive estimates.
Views: 224Downloads: 63

Downloads

Download data is not yet available.

References

ALI, M. U. et al. Towards a smarter battery management system for electric vehicle applications: A critical review of lithium-ion battery state of charge estimation. Energies, v. 12, n. 3, art. 446, 2019. DOI: 10.3390/en12030446. DOI: https://doi.org/10.3390/en12030446

CESPEDES, M.; XING, L.; SUN, J. Constant-power load system stabilization by passive damping. IEEE Transactions on Power Electronics, v. 26, n. 7, p. 1832–1836, 2011. DOI: 10.1109/TPEL.2011.2151880. DOI: https://doi.org/10.1109/TPEL.2011.2151880

CHEN, Haonan et al. Edge intelligence for space-air-ground integrated network. Chinese Journal of Aeronautics, v. 39, n. 8, art. 103969, 2026. DOI: 10.1016/j.cja.2025.103969. DOI: https://doi.org/10.1016/j.cja.2025.103969

FORTESCUE, Peter; SWINERD, Graham; STARK, John (eds.). Spacecraft systems engineering. 4. ed. Chichester: Wiley, 2011. ISBN: 978-0-470-75012-4. DOI: 10.1002/9781119971009. DOI: https://doi.org/10.1002/9781119971009

FUJII, H.; ABE, T. Current collection and discharges on high voltage solar array for space use in plasma. IEEE Transactions on Plasma Science, v. 31, n. 5, p. 1001–1005, 2003. DOI: 10.1109/TPS.2003.818448. DOI: https://doi.org/10.1109/TPS.2003.818448

GROVER, Frederick W. Inductance Calculations: Working Formulas and Tables. New York: Dover Publications, 1946.

HILLARD, G. B.; FERGUSON, D. C. LEO Spacecraft Charging Design Guidelines. NASA/TM—2003-212737. Cleveland: NASA Glenn Research Center, 2003.

HOSODA, S. et al. Development of 400 V solar array technology for low earth orbit plasma environment. IEEE Transactions on Plasma Science, v. 34, n. 5, p. 1986–1996, 2006. DOI: 10.1109/TPS.2006.883287. DOI: https://doi.org/10.1109/TPS.2006.883287

IWASA, Minoru et al. Study of the plasma interference with high-voltage electrode array for space power application. IEEE Transactions on Plasma Science, v. 34, n. 5, p. 1997–2003, 2006. DOI: 10.1109/TPS.2006.883369. DOI: https://doi.org/10.1109/TPS.2006.883369

KOPP, G.; LEAN, J. L. A new, lower value of total solar irradiance. Geophysical Research Letters, v. 38, n. 1, L01706, 2011. DOI: 10.1029/2010GL045777. DOI: https://doi.org/10.1029/2010GL045777

LYDEN, Sarah; HAQUE, Md. Enamul. Maximum Power Point Tracking techniques for photovoltaic systems. Renewable and Sustainable Energy Reviews, v. 52, p. 1504–1518, 2015. DOI: 10.1016/j.rser.2015.07.172. DOI: https://doi.org/10.1016/j.rser.2015.07.172

MALIK, M. Z. et al. Investigation of MPPT techniques under uniform and non-uniform solar irradiation condition. IEEE Access, v. 8, p. 127368–127392, 2020. DOI: 10.1109/ACCESS.2020.3007710. DOI: https://doi.org/10.1109/ACCESS.2020.3007710

MIDDLEBROOK, R. D. Input filter considerations in design and application of switching regulators. In: IEEE Power Electronics Specialists Conference (PESC), 1976, Cleveland. Proceedings... Piscataway: IEEE, 1976. p. 366–382.

ORTIZ DEL CASTILLO, M. et al. Unlocking the potential of small satellites. arXiv, 2024. arXiv:2407.14031. DOI: 10.48550/arXiv.2407.14031.

PATEL, M. R. Spacecraft power systems. Boca Raton: CRC Press, 2004. ISBN: 978-0-8493-2086-6. DOI: 10.1201/9780203502808.

PAUL, Clayton R. Analysis of Multiconductor Transmission Lines. 2. ed. Hoboken: Wiley-IEEE Press, 2007. ISBN: 978-0-470-13145-9.

PLETT, G. L. Extended Kalman filtering for battery management systems of LiPB-based HEV battery packs: Part 1. Background. Journal of Power Sources, v. 134, n. 2, p. 252–261, 2004. DOI: 10.1016/j.jpowsour.2004.02.031. DOI: https://doi.org/10.1016/j.jpowsour.2004.02.031

RADWAN, A. A. A.; MOHAMED, Y. A.-R. I. Linear active stabilization of converter-dominated DC microgrids. IEEE Transactions on Smart Grid, v. 2, n. 1, p. 203–216, 2011. DOI: 10.1109/TSG.2010.2093035. DOI: https://doi.org/10.1109/TSG.2011.2162430

RADWAN, A. A. A.; MOHAMED, Y. A.-R. I. Modeling, analysis, and stabilization of converter-fed AC microgrids. IEEE Transactions on Smart Grid, v. 3, n. 3, p. 1213–1225, 2012. DOI: 10.1109/TSG.2012.2191986. DOI: https://doi.org/10.1109/TSG.2012.2183683

RICCOBONO, A.; SANTI, E. Comprehensive review of stability criteria for DC power distribution systems. IEEE Transactions on Industry Applications, v. 50, n. 5, p. 3525–3535, 2014. DOI: 10.1109/TIA.2014.2309881. DOI: https://doi.org/10.1109/TIA.2014.2309800

SCHNUR, J. et al. Megawatt-scale power electronics for electrified aircraft and aerospace platforms: Technical evaluation and high-power density benchmarks. NASA/TM—20210018245. Cleveland: NASA Glenn Research Center, 2021.

SUBUDHI, B.; PRADHAN, R. A comparative study on maximum power point tracking techniques for photovoltaic power systems. IEEE Transactions on Sustainable Energy, v. 4, n. 1, p. 89–98, 2013. DOI: 10.1109/TSTE.2012.2202294. DOI: https://doi.org/10.1109/TSTE.2012.2202294

SUN, J. Impedance-based stability criterion for grid-connected inverters. IEEE Transactions on Power Electronics, v. 26, n. 11, p. 3075–3078, 2011. DOI: 10.1109/TPEL.2011.2136439. DOI: https://doi.org/10.1109/TPEL.2011.2136439

TALEBZADEH, Sarah; BEIK, Omid. Medium voltage DC system for large spacecraft megawatt-scale power and propulsion systems. Electronics, v. 13, n. 10, art. 1810, 2024. DOI: 10.3390/electronics13101810. DOI: https://doi.org/10.3390/electronics13101810

THALES ALENIA SPACE. ASCEND: Advanced Space Cloud for European Net zero Emission and Data Sovereignty. Comunicado oficial / Horizon Europe Project 101082192, 27 jun. 2024.

VAN DER MERWE, R.; WAN, E. A. The square-root unscented Kalman filter. In: IEEE International Conference on Acoustics, Speech, and Signal Processing (ICASSP), 2001, Salt Lake City. Proceedings... Piscataway: IEEE, 2001. v. 6, p. 3461–3464. DOI: 10.1109/ICASSP.2001.940586. DOI: https://doi.org/10.1109/ICASSP.2001.940586

VARSHNI, Y. P. Temperature dependence of the energy gap in semiconductors. Physica, v. 34, n. 1, p. 149–154, 1967. DOI: 10.1016/0031-8914(67)90062-6. DOI: https://doi.org/10.1016/0031-8914(67)90062-6

WAN, E. A.; VAN DER MERWE, R. The unscented Kalman filter for nonlinear estimation. In: IEEE Adaptive Systems for Signal Processing, Communications, and Control Symposium (AS-SPCC), 2000, Lake Louise. Proceedings... Piscataway: IEEE, 2000. p. 153–158. DOI: 10.1109/ASSPCC.2000.882463. DOI: https://doi.org/10.1109/ASSPCC.2000.882463

XIONG, R.; LI, L.; TIAN, J. Towards a smarter battery management system: A critical review on battery state of health monitoring methods. Journal of Power Sources, v. 405, p. 18–29, 2018. DOI: 10.1016/j.jpowsour.2018.10.019. DOI: https://doi.org/10.1016/j.jpowsour.2018.10.019

Published

2026-11-12

How to Cite

Castro de Martins Barros, D. T., & Barcelos Braz da Silva, F. (2026). Coupled Electro-Thermal and Storage Dynamics of AM0 Photovoltaic Systems Supplying Megawatt-Scale Space Data Centers: A Simulation-Based Design Study. REMUNOM, 13(23), 1-29. https://doi.org/10.66104/sdhm5c86

Similar Articles

1-10 of 50

You may also start an advanced similarity search for this article.